| Place of Origin |
China |
| Brand Name |
DINWAY |
| Model Number |
ID |
| Type |
Residual Current |
ID RCCB PARAMETER RATINGTypeElectro-magneticNumber of poles2P4PRated making and breaking capacity630ARated Current(In)25,40,63,80,100ARated Voltage(Un)AC 2P: 230/240V 4P: 400/415VRated residual operating current( In)30100300500mARated residual non-operation Current( Ino)0.5InResidual operating current scope0.5In InResidual current breaking time≤0.3sResidual current trip characteristicsA,ACUltimate short-circuit breaking capacity (Inc)6000AEndurance≥4000Connection Capacity≤25mm2Connection terminal torque (Max.)2.0NmDegree of protectionIP20StandardIEC/EN610018 Many other types of RCBO, residual current device are also available